Command Set | 5017/5018 Analog Input | |
|
|
|
$aaSi1 |
| $aaSi1 |
Name | Zero Calibration |
|
Description | Calibrates a specified analog input module to correct for | |
| offset errors |
|
Syntax | $aaSi1(cr) |
|
| $ is a delimiter character. | |
| aa (range | |
| address of the | |
| calibrated. |
|
| Si identifies the I/O slot which is to be calibrated. | |
| 1 represents the zero calibration command. | |
| (cr) is the terminating character, carriage return (0Dh) | |
Response | !aa(cr) if the command is valid. | |
| ?aa(cr) if an invalid operation was entered. | |
There is no response if the module detects a syntax error or communication error or if the specified address does not exist.
! delimiter character indicating a valid command was received.
? delimiter character indicating the command was invalid.
aa (range
(cr) is the terminating character, carriage return (0Dh)
Note: In order to successfully calibrate an analog input module's input range, a proper calibration input signal should be connected to the analog input module before and during the calibration process. (See also Chapter 4, Section 4.5 on Calibration)