5013/5017/5017H/5018

Command Set

Analog Input Alarm

 

 

$aaSiCjAhCSkCn

$aaSiCjAhCSkCn

Name

Set Alarm Connection

Description

Connects the High/Low alarm of the specified input

 

channel to the specified digital output in the addressed

 

ADAM-5000 system

Syntax

$aaSiCjAhCSkCn(cr)

 

$ is a delimiter character.

 

aa (range 00-FF) represents the 2-character hexadecimal

 

address of an ADAM-5000 system.

 

SiCj identifies the desired slot i (i : 0 to 3) and the

 

desired analog input channel j (j : 0 to 7).

 

AhC is the Set Alarm Connection command.

 

h indicates alarm type and can have the value H = High

 

alarm, L = Low alarm

 

SkCn identifies the desired slot k (k : 0 to 3) and the

 

desired digital output point n (n : 0 to F). To disconnect

 

the digital output, k and n should be set as ‘*’.

 

(cr) represents terminating character, carriage return

 

(0Dh)

Response

!aa(cr) if the command was valid

 

There is no response if the system detects a syntax error

 

or communication error or if the specified address does

 

not exist.

 

! delimiter character indicating a valid command was

 

received.

 

aa represents the 2-character hexadecimal address of the

 

corresponding ADAM-5000 system.

 

(cr) represents terminating character, carriage return

 

(0Dh)

6-80

ADAM-5000

Page 202
Image 202
Advantech RS-485 user manual Syntax $aaSiCjAhCSkCncr