Chapter 6

 

 

$aaSiB

$aaSiB

Name

RTD Configuration Status

Description

Returns the configuration parameters for a specified

 

RTD input module in a specified system.

Syntax

$aaSiB(cr)

 

$ is a delimiter character.

 

aa (range 00-FF) represents the 2-character hexadecimal

 

address of the ADAM-5000 system you want to

 

interrogate.

 

Si identifies the desired slot i (i:0to3)

 

B represents the configuration status command

 

(cr) is the terminating character, carriage return (0Dh).

Response.

!aarrff(cr) if the command is valid.

 

?aa(cr) if an invalid operation was entered.

 

There is no response if the module detects a syntax error

 

or communication error or if the specified address does

 

not exist.

 

! delimiter character indicating a valid command was

 

received.

 

? delimiter character indicating the command was

 

invalid.

 

aa (range 00-FF) represents the 2-character hexadecimal

 

address of an ADAM-5000 system.

 

rr represents the 2-character hexadecimal code of the

 

input range. (See Appendix B)

 

ff is a hexadecimal number that equals the 8-bit parame-

 

ter representing data format. Bits 0 and 1 represent data

 

format. Bit 7 represents integration time (See RTD

 

Configuration Command $aaSiArrff).

ADAM-5000

6-23