Appendix A - Advanced Display Module (ADM)

Attempting to dispense from multiple valves simultane- ously using any other combination will cause an Incom- patible Valves Settings alarm.

Fluid Plate x, Screen 3 (Delay Settings)

This screen enables users to set on and off delays (in milliseconds) for each valve and the regulator. For an explanation of the on and off delays, refer to the On/Off Delays section on page 39.

Fluid Plate x, Screen 4 (Control Loop and Flowmeter Settings)

This screen enables users to set the meter type (volume or mass) and the K-Factor for the flowmeter. Users can also set the Kp, Ki, and Kd for the pressure control loop as well as Kp and Ki for bead control loop.

NOTE: In systems without a flow meter, the flow meter settings will be grayed out.

NOTE: It is recommended that these values not be changed from the factory defaults of 32.00 for Kp, 128.00 for Ki, and 0.00 for Kd.

106

3A2098H

Page 106
Image 106
Graco 3A2098H Fluid Plate x, Screen 3 Delay Settings, Fluid Plate x, Screen 4 Control Loop and Flowmeter Settings