Troubleshooting

Troubleshooting

NOTE: Check all possible solutions in the chart below before you disassemble the system.

Troubleshooting for individual fluid regulators and flow meters is also discussed in their separate manuals; refer to Related Manuals on page 3. Also refer to Event and Error Codes and Troubleshooting, page 67, for detailed information on how error codes are communi- cated.

Fluid Plates

Problem

Cause

Solution

 

 

 

 

 

 

 

No outlet pressure

Air pressure low

Verify air pressure is above 60 psi

 

 

 

(410 kPa, 4.1 bar)

 

 

 

 

No “Valve On” signal from automation

Check output and wiring from auto-

 

unit

mation unit

 

 

 

 

No air signal to air diaphragm

Check for loose/disconnected con-

 

 

nector to Voltage to Pressure (V/P)

 

 

Transducer; tighten

 

 

 

 

False signal being sent to control

Check outlet pressure sensor output;

 

 

verify that it corresponds to zero

 

 

pressure; replace sensor and/or

 

 

amplifier

 

 

 

High outlet pressure

Fluid regulator needle/seat is worn

Rebuild fluid regulator; replace nee-

 

 

dle/ seat

 

 

 

Air leaks from fluid plate

Loose air connections

Check air connections; tighten if nec-

 

 

essary

 

 

 

 

Worn gaskets

Check/replace gaskets on Voltage to

 

 

Pressure (V/P) Transducer and sole-

 

 

noid valve

 

 

 

 

62

3A2098H

Page 62
Image 62