Troubleshooting

 

 

 

 

 

 

Motor not responding to change in

 

No “Swirl Speed Command” signal

Check input from automation unit

speed command

 

 

from automation unit

 

 

 

 

 

 

 

 

 

 

Swirl speed source incorrectly set

Verify Speed Command Source in

 

 

 

 

 

Swirl Setup screen

 

 

 

 

 

 

Gateway Module

 

 

 

 

 

 

 

Problem

Cause

 

Solution

 

 

 

 

No communication

Incorrect wiring

 

Check wiring per fieldbus standard. Refer to PCF Gateway

 

 

 

 

LED status indicators and Appendix C - Communications

 

 

 

 

Gateway Module (CGM) Connection Details, page 122.

 

 

 

 

Incorrect fieldbus settings

Confirm fieldbus settings at automation controller (fieldbus

 

 

 

 

master) and PCF Gateway (fieldbus slave). Refer to Appen-

 

 

 

 

dix A - Advanced Display Module (ADM), page 99, for infor-

 

 

 

 

mation on PCF Gateway configuration settings.

 

 

 

Incorrect data

Incorrect fieldbus configu-

Download PCF fieldbus configuration file from

 

ration file installed on

www.graco.com, and install on automation controller (fieldbus

 

automation controller

master).

 

 

(fieldbus master)

 

 

 

 

 

 

Incorrect map installed on

Confirm correct PCF data map is installed on PCF Gateway.

 

PCF Gateway

 

Refer to Appendix A - Advanced Display Module (ADM),

 

 

 

 

page 99, for information on how to determine installed data

 

 

 

 

map. If necessary, install a new Gateway data map. Refer to

 

 

 

 

Upgrade Gateway Module Fieldbus Map, page 78, for

 

 

 

 

instructions, and Control Center and Expansion Swirl

 

 

 

 

Enclosure Parts, page 92, for map token part number.

 

 

 

 

 

 

LED Diagnostic Information

The following LED signals, diagnosis, and solutions apply to the Advanced Display Module, Fluid Control Module, and Gateway module.

Module Status LED Signal

Diagnosis

Solution

 

 

 

 

 

 

Green on

System is powered up

-

 

 

 

Yellow

Internal communication in progress

-

 

 

 

Red solid

Hardware failure

Replace module

 

 

 

Red flashing fast

Uploading software

-

 

 

 

Red flashing slow

Token error

Remove token and upload software

 

 

token again.

 

 

 

Red flashes three times, pauses,

Invalid rotary switch position (FCM

Change rotary switch position to a

then repeats

and DGM only)

valid position then restart the system.

 

 

See page 15.

 

 

 