Graco 3A2098H Install Fieldbus Connections, State Description Comments, Run, Stop

Models: 3A2098H

1 142
Download 142 pages 28.28 Kb
Page 122
Image 122

Appendix C - Communications Gateway Module (CGM) Connection Details

Appendix C - Communications Gateway Module (CGM) Connection Details

Install Fieldbus Connections

Connect cables to fieldbus per fieldbus standards.

PROFINET

 

MS

NS

Link

 

TI11814A

FIG. 69: PROFINET Fieldbus Connections

The Ethernet interface operates at 100Mbit, full duplex, as required by PROFINET. The Ethernet interface is auto-polarity sensing and auto-crossover capable.

Network Status (NS)

State

Description

Comments

 

 

 

Off

Offline

No power

 

 

No connection with IO

 

 

Controller

 

 

 

Green

On-line,

Connection with IO Con-

 

(RUN)

troller established

 

 

IO Controller with RUN

 

 

state

 

 

 

Flashing

On-line,

Connection with IO Con-

Green

(STOP)

troller established

 

 

IO Controller in STOP

 

 

state

 

 

 

Module Status (MS)

State

Description

Comments

 

 

 

Off

Not initial-

No power or module in

 

ized

“SETUP” or “NW_INIT” state

 

 

 

Green

Normal

Diagnostic event(s) present

 

operation

 

 

 

 

Flashing

Initialized,

Used by engineering tools to

Green

diagnostic

identify node on network

 

event(s)

 

 

present

 

 

 

 

Red

Exception

Module in state “EXCEPTION”

 

error

 

 

 

 

Red (1

Configura-

Expected Identification differs

flash)

tion error

from Real Identification

 

 

 

Red (2

IP Address

Set IP address via system

flashes)

not set

monitor or DNS server

 

 

 

Red (3

Station

Set Station Name via system

flashes)

Name not

monitor

 

set

 

 

 

 

Red (4

Major Inter-

Cycle system power; replace

flashes)

nal Error

module

 

 

 

Link/Activity (Link)

State

Description

 

 

Off

No Link, no communication present

 

 

Green

Link established, no communication present

 

 

Green,

Link established, communication present

flashing

 

 

 

122

3A2098H

Page 122
Image 122
Graco 3A2098H important safety instructions Install Fieldbus Connections, State Description Comments, Run, Stop