Graco 3A2098H Install Gateway Module Interface, Fieldbus Communications Gateway Module

Models: 3A2098H

1 142
Download 142 pages 28.28 Kb
Page 30
Image 30

Installation

Install Gateway Module Interface

NOTE: Systems with swirl dispensers will have two gateway modules in the control center. The gateway module on the left is the swirl control DGM module, and does not need any setup or modification. The gateway module on the right is the automation Gateway module. This section covers the automation Gateway module.

Fieldbus Communications Gateway Module

Module Description

The Communications Gateway Module (CGM) provides a control link between the PCF system and a selected fieldbus. This provides the means for remote monitoring and control by external automation systems.

See Automation Control (Normal Operation), page 45, for details on controlling the PCF system through the Gateway module.

Data Exchange

Data is available by block transfer, cyclic transfer, change of state triggered, and explicit access to individ- ual attributes as defined by the fieldbus specification. Refer to Appendix C - Communications Gateway Module (CGM) Connection Details, page 138, for details about PCF/fieldbus data map.

NOTE: The following system network configuration files are available at www.graco.com

EDS file: DeviceNet or EtherNet/IP fieldbus net- works

GSD file: PROFIBUS fieldbus networks

SDML: PROFINET fieldbus networks

CGM Status LED Signals

Signal

Description

 

 

Green on

System is powered up

 

 

Yellow

Internal communication in progress

 

 

Red

CGM hardware failure

Solid

 

 

 

*Red

Data map load failure

(7 flashes)

 

Incorrect data map for fieldbus type

 

 

 

 

No data map loaded

 

 

*The red LED (CF) will flash a code, pause, then repeat.

Installation

NOTE: The following installation instructions assume the person implementing the PCF fieldbus connection fully comprehends the fieldbus being used. Ensure the installer understands the automation controller commu- nication architecture and the fieldbus being used.

1.Install interface cables between the PCF system and the automation controller per the fieldbus stan- dards. Refer to Appendix C - Communications Gateway Module (CGM) Connection Details, page 122, for details.

2.Turn on system power. Navigate to the Gateway setup screens and ensure the data map name is: PCF 4FP. Refer to Appendix A - Advanced Dis- play Module (ADM), page 99, for details about the data map.

3.Set the PCF Gateway configuration values as required to interface with automation controller. Refer to Appendix A - Advanced Display Module (ADM), page 99, for details about the configuration settings.

4.Retrieve the appropriate fieldbus configuration file for the fieldbus being used from www.graco.com.

5.Install the configuration file on the automation con- troller (fieldbus master). Configure it for communica- tion with the PCF Gateway (fieldbus slave).

6.Establish communication between the automation controller and the PCF Gateway to confirm the suc- cessful configuration of the hardware and data.

NOTE: Use the ADM screens for troubleshooting field- bus data communication problems. Refer to Appendix A - Advanced Display Module (ADM), page 99, for details. Also, use the LED status indicators on the PCF Gateway module for fieldbus status information. Refer to

Appendix C - Communications Gateway Module (CGM) Connection Details, page 122, for details.

30

3A2098H

Page 30
Image 30