Setup Maintenance

Schedule/Parameters

Set the volume (or hours) limit that will trigger a mainte- nance advisory for the fluid supply, Voltage to Pressure (V/P) Transducer, fluid regulator, flow meter, and all four valves.

NOTE: Hours is shown instead of Volume for fluid plates without a flow meter.

The Volume (or Hours) column displays the current totalizer value. If this value exceeds the set limit, the value will turn red and a maintenance advisory is issued. See Fluid Plate x, Screen 7 (Maintenance Advisory Limits), page 108, for more information about mainte- nance totalizers.

To set limits:

1.With the system in setup mode, navigate to the Fluid Plate x, screen 7 (Maintenance Advisory Limits).

2.Press to access the fields to make changes.

FIG. 26

3.Enter the desired limit for the air supply and press

to enter the selection.

4.Press to move to the next field. Repeat Step 4 for each field.

5.Press to exit edit mode.

System Setup

To reset a totalizer value:

1.Follow Steps 1-3 of To set limits: to make changes in Fluid Plate x, screen 7 (Maintenance Advisory Lim- its).

2.Press to scroll to the system component to reset.

3. Press

to reset the value.

Configure Valve to Swirl Association and Motor Error Type

Define which Swirl number is installed on which dis- pense valve.

Set the error type (alarm or deviation) that will be issued if a motor fault occurs. When an alarm occurs, the fluid plate stops dispensing. When a deviation occurs, the fluid plate will continue dispensing.

FIG. 27

3A2098H

37

Page 37
Image 37
Graco 3A2098H Setup Maintenance Schedule/Parameters, Configure Valve to Swirl Association and Motor Error Type