Image 97

SNC 5100

If you need to set a netmask, specify it after the network address:

Example:

foster > ethAddrSet “10.0.0.2”, “255.0.0.0”

If you need a network route and/or default gateway, you must specify it.

Example:

foster > gateAddrSet "192.168.1.1" value = 0 = 0x0

When more complicated routing is required, use the route command to specify the destination address, as a full address (single host) or as an abbreviated subnet address.

Specify the address of the gateway that is reachable on the local subnet.

Example:

foster > route "add", "206.0.0", "192.168.1.1" value = 0 = 0x0

Step 4. Optionally, add User account for Telnet

If you want to access the SNC 5100’s command line interface through its Ethernet port using a Telnet session, you need to add a user account.

The user name you specify must be 3 or more characters. The password you specify must be 8 or more characters.

For more information, see the commands beginning with user in the “Service Port Command Reference” on page 105.

Example:

foster > userAdd “username”,”password” value = 0 = 0x0

foster >

Step 5. Enter the reboot command to reboot the SNC 5100:

For more information, see the "ethAddrSet" command on page 121.

Example: foster > reboot

Network Setup for the SNC 5100

89

6-00020-02

Page 97