SNC 5100

Updating the SNC 5100

Step 1. From the service terminal, enter the normalBoot command.

For more information, see the "normalBoot" command on page 191.

Step 2. Wait until the SNC 5100 has finished booting.

Step 3. From the service terminal, enter the version command.

For more information, see the "version" command on page 185.

Step 4. Write down the operating software version number.

Step 5. Determine whether the SNC 5100’s firmware version requires an update.

If an update is required, download the new file or files and the associated readme.

You will install the new firmware as you complete the "Post-Repair

Checklist".

Step 6. If you replaced the SNC 5100, enter the ridTag command and type the identifier.

Caution

You must perform this step if you replaced the SNC 5100.

For more information, see the "ridtag [“value”]" command on page 152.

Step 7. Shut down the SNC 5100.

Step 8. Unplug the power cord.

Step 9. Disconnect the RS-232 cable from the SNC 5100.

Step 10. Proceed to "Post-Repair Checklist".

90 Updating the SNC 5100

6-00020-02