CAUTION: Baldor does not recommend using “Grounded Leg Delta” transformer power leads that may create earth/ground loops and degrade system performance. Instead, we recommend using a four wire Wye.
CAUTION: Drives are intended to be connected to a permanent main power source, not a portable power source. Suitable fusing and circuit protection devices are required.
CAUTION: The safe integration of the drive into a machine system is the responsibility of the machine designer. Be sure to comply with the local safety requirements at the place where the machine is to be used. In Europe these are the Machinery Directive, the ElectroMagnetic Compatibility Directive and the Low Voltage Directive. In the United States this is the National Electrical code and local codes.
CAUTION: Drives must be installed inside an electrical cabinet that provides environmental control and protection. Installation information for the drive is provided in this manual. Motors and controlling devices that connect to the drive should have specifications compatible to the drive.
CAUTION: Failure to meet cooling air flow requirements will result in reduced product lifetime and/or drive overtemperature trips.
CAUTION: Violent jamming (stopping) of the motor during operation may damage the motor and drive.
CAUTION: Operating the MicroFlex e100 in Torque mode with no load attached to the motor can cause the motor to accelerate rapidly to excessive speed.
CAUTION: If the drive enable signal is already present when power is applied to the MicroFlex e100, the motor could begin to move immediately.
CAUTION: Do not tin (solder) exposed wires. Solder contracts over time and may cause loose connections. Use crimp connections where possible.
CAUTION: Electrical components can be damaged by static electricity. Use ESD (electrostatic discharge) procedures when handling this drive.
CAUTION: Ensure that encoder wires are properly connected. Incorrect installation may result in improper movement.
CAUTION: The threaded holes in the top and bottom of the case are for cable clamps. The holes are 11.5 mm deep and accept M4 screws, which must be screwed in to a depth of at least 8mm.
CAUTION: Removing the cover will invalidate UL certification.
CAUTION: The metal heatsink on the left side of the MicroFlex e100 can become very hot during normal operation.