3.4.8 24Vcontrol circuit supply
A24VDC supplymust be provided to power thecontrolling electronics . This is useful for safety
reasons where AC power needs to be removed from the power stage but the controlling
electronics must remain powered to retain position and I/O information.
A separate fused 24V supply should be prov ided for the MicroFlex e100. If other devices are
likely to be powered from the same 24V supply, a filter (Baldor catalog number FI0014A 00)
should be installed to isolate the MicroFlex e100 from the rest of the s ystem. Alternatively, a
ferrites leeve may be attached to the supply cable near connector X2.
Location Connector X2
Nominalinput
voltage
24V
Range 20-30VDC
Inputcurrent
Maximum
Typica l
1Acontinuous (4A ty pical power on surge, limited by NTC)
0.5A - 0.6A (not powering feedback device)
0.6A - 0.8A (powering feedback device)
Tighteningtorque for terminal bloc k connections is 0.5-0.6Nm (4.4-5.3 lb-in).
Customersupplied
24VDC
GND
24Vfilter
(optional)
+24V
STAR
POINT
Incomingsafety
earth/ground(PE)
*Recommended fuse: BussmanS504 20x5mm anti-surge 2A.
**Recommended ferrite sleeve: Fair-Ritepart 0431164281or si milar.
Usea twisted pair cable, with
ferritesleeve attached close
toconnector X2.
Ferrite
sleeve**
Fuse*
Figure6 - 24V control circuit supply connections