3-18 BasicInstallation MN1942

3.5 Motor connections
MicroFlex e100 will operate with a large number of brushless servo motors. For information on
selectingBaldor servomotor s please see the sales broc hure BR1202, available from your local
Baldorrepresent ative. The motor must be capable of being powered by an inverter PWMoutput
- see section 8.1.3 for details. The motor can be connected directly to the MicroFlex e100 or
througha motor contac tor (M-Contactor). The motor output s are conditionally short -circuit proof.
Motors should ideally have a minimum inductance of 1mH per winding; for motors with lower
inductance an output reactor may be fitted in series with the motor.
When using a Baldor motor, the parameters for managing motor overloads are configured
automatically by the Commissioning Wizard (see sec tion 6.4.3). If they need to be changed, or
you are using an alternative motor, use the Parameters tool in Mint WorkBench (see sect ion
6.5.2).
Location Connector X1
ACsupply voltage 115VAC,1Φ230VAC, 1Φ230VAC, 3Φ
Outputvoltage range 0-115VAC,3Φ0-230VAC, 3Φ0-230VAC, 3Φ
Unshielded
lengthsshould
beas short as
possible.
V
W
U
Motor
Toearth/groundouter
shield,use 360°
clampconnected to
backplane.
Optionalmotor
circuitcontactors.
Toearth/ground
outershield,
use360° clamp
connectedto
backplane.
Earth
Connectmotor
earth/ground
toprotective
earthon top of
drive.
Figure7 - Motor connections
CAUTION: Do not connect supply power to the MicroFlex e100 UVW outputs . The
MicroFlex e100 might be damaged.
CAUTION: The motor leads U, V and W must be connected to their corres ponding U,
Vor W terminal on the motor. Misconnection will r esult in uncontrolled motor
movement.
Themotor power cable must be shielded for CE compliance.The connec tor or glandus ed atthe
motor must provide 360 degree shielding. The maximum recommended cable length is 30.5m
(100ft).
Note: For CE compliance the motor earth/ground should be connected to the driv e
earth/ground.