7.2.3 ETHERNET LEDs

The ETHERNET LEDs display the overall condition of the Ethernet interface once the startup sequence has completed. The LED codes conform to the ETHERNET Powerlink Standardization Group (EPSG) standard at the time of production.

Green (status)

XOff: Node in NOT ACTIVE state. The controlled node is waiting to be triggered by the manager node.

1 flash: Node in PRE-OPERATIONAL1 state. EPL mode is starting.

2 flashes: Node in PRE-OPERATIONAL2 state. EPL mode is starting.

3 flashes: Node in READY TO OPERATE state. The node is signalling its readiness to operate.

Blinking (continuous flashing): Node in STOPPED state. The controlled node has been deactivated.

Flickering (very fast flashing): Node in BASIC ETHERNET state (EPL is not operating, but other Ethernet protocols may be used).

Continuously illuminated, not flashing: Node in OPERATIONAL state. EPL is operating normally.

Red (error)

XOff: EPL is working correctly.

Continuously illuminated: An error has occurred.

7-4 Troubleshooting

MN1942

Page 96
Image 96
Baldor E100 manual Ethernet LEDs, Green status