Chapter 6 Control Modes of OperationASDA-AB Series

Allowable frequency when the servo motor run without load (times/min)

 

ECMA Series

500W

600W

750W

900W

1.0kW

 

(100 mm)

Regenerative

 

 

 

 

05

06

07

09

10

Resistors

BR400W040

291

283

2128

213

925

BR1K0W020

729

708

5274

533

2312

ECMA Series

1.0kW

1.5kW

2.0kW

2.0kW

2.0kW

 

(130mm)

(100mm)

(130mm)

(180mm)

Regenerative

 

10

15

20

20

20

Resistors

BR400W040

283

213

562

163

68

BR1K0W020

708

533

1363

408

171

( ) : motor frame size, unit is in millimeters.

 

 

 

 

6.6.4 Analog Monitor

User can use analog monitor to observe the required analog voltage signals. ASDA-AB series provide two analog channels, they are PIN No. 15 and 16 of CN1 connector. The parameters relative to analog monitor are shown below.

Relevant parameters:

P0 - 03

 

MON

Analog Monitor Output

Communication Addr.: 0003H

 

 

 

 

 

 

 

 

 

Default: 01

Related Section:

Applicable Control Mode: P/S/T

Section 4.3.5

Unit: N/A

 

 

 

 

 

 

Range: 00 ~ 55

 

Settings:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A: CH1

B: CH2 not used

AB: (A: CH1; B: CH2)

0:Motor speed (+/-8 V/maximum rotation speed)

1:Motor torque (+/-8 V/maximum torque)

2:Pulse command frequency (+8 Volts /650Kpps)

3:Speed command (+/-8 Volts /maximum speed command)

4:Torque command (+/-8 Volts /maximum torque command)

5:V_BUS voltage (+/-8 Volts /450V)

Note: For the setting of analog output voltage proportion, refer to the P1-04 and P1-05

6-40

Revision March 2008, Doc. Name: 2007PDD23000011

Page 143
Image 143