Chapter 5 Trial Run and Tuning ProcedureASDA-AB Series

5.4Speed Trial Run without Load

Before speed trial run, fix and secure the motor as possible to avoid the danger from the reacting force when motor speed changes.

STEP 1:

Set the value of parameter P1-01 to 02 and it is speed (S) control mode. After selecting the operation mode as speed (S) control mode, please restart the drive as P1-01 is effective only after the servo drive is restarted (after switching power off and on).

STEP 2:

In speed control mode, the necessary Digital Inputs are listed as follows:

Digital Input

Parameter Setting

Sign

Function Description

CN1 PIN No.

Value

 

 

 

 

DI1

P2-10=101

SON

Servo On

DI1-=9

 

 

 

 

 

DI2

P2-11=109

TRQLM

Torque limit enabled

DI2-=10

 

 

 

 

 

DI3

P2-12=114

SPD0

Speed command selection

DI3-=34

 

 

 

 

 

DI4

P2-13=115

SPD1

Speed command selection

DI4-=8

 

 

 

 

 

DI5

P2-14=102

ARST

Reset

DI5-=33

 

 

 

 

 

DI6

P2-15=0

Disabled

This DI function is disabled

-

 

 

 

 

 

DI7

P2-16=0

Disabled

This DI function is disabled

-

 

 

 

 

 

DI8

P2-17=0

Disabled

This DI function is disabled

-

 

 

 

 

 

By default, DI6 is the function of reverse inhibit limit, DI7 is the function of forward inhibit limit and DI6 is the function of emergency stop (DI8), if the users do not set the setting value of parameters P2-15 to P2-17 to 0 (Disabled), the faults (ALE13, 14 and 15) will occur (For the information of fault messages, please refer to Chapter 10). Therefore, if the users do not need to use these three digit inputs, please set the setting value of parameters P2-15 to P2-17 to 0 (Disabled) in advance.

All the digital inputs of Delta ASDA-AB series are user-defined, and the users can set the DI signals freely. Ensure to refer to the definitions of DI signals before defining them (For the description of DI signals, please refer to Table 7.A in Chapter 7). If any alarm code displays after the setting is completed, the users can restart the drive or set DI5 to be activated to clear the fault. Please refer to section 5.2.

The speed command is selected by SPD0, SPD1. Please refer to the following table:

Speed

DI signal of CN1

Command Source

Content

Range

Command No.

 

 

SPD1

SPD0

 

 

 

 

 

 

 

S1

0

0

External analog

Voltage between V-REF

+/-10V

command

and GND

 

 

 

 

S2

0

1

 

P1-09

0 ~ 5000r/min

S3

1

0

Internal parameter

P1-10

0 ~ 5000r/min

S4

1

1

 

P1-11

0 ~ 5000r/min

0: indicates OFF (Normally Open); 1: indicates ON (Normally Closed)

Revision March 2008, Doc. Name: 2007PDD23000011

5-9