Chapter 6 Control Modes of OperationASDA-AB Series

2)So if user change the control mode to Pr mode and switching power off and on, the servo drive of parameter P1-36 will auto set the value to 20.

6.2.5Electronic Gear Ratio

Relevant parameters:

P1 - 44▲

GR1

Electronic Gear Ratio (1st Numerator) (N1)

Communication Addr.: 012CH

Default: 1

Related Section:

Applicable Control Mode: P

Section 6.2.5

Unit: Pulse

 

Range: 1 ~ 32767

 

Settings:

Multiple-step electronic gear numerator setting. Please refer to P2-60~P2-62.

P1 - 45▲

GR2

Electronic Gear Ratio (Denominator)

Communication Addr.: 012DH

 

 

 

Default: 1

 

Related Section:

Applicable Control Mode: P

Section 6.3.6

Unit: Pulse

 

Range: 1 ~ 32767

 

Settings:

Electronic gear denominator setting.

Please set electronic gear ratio when the servo drive is Off. As the wrong setting can cause motor to run chaotically (out of control) and it may lead to personnel injury, therefore, ensure to observe the following rule when setting P1-44, P1-45.

The electronic gear ratio setting (Please also see P1-44, P2-60~P2-62):

Pulse input

 

 

 

 

Position

 

f1: Pulse input

f2: Position command

 

 

N

 

command

 

N: Numerator 1, 2, 3, 4, the setting value of P1-44 or

 

 

 

M

 

 

 

 

f1

 

f2 = f1 x

N

 

 

 

 

 

 

P2-60 ~ P2-63

 

 

 

 

 

 

M

 

 

M:Denominator, the setting value of P1-45

The electronic gear ratio setting range must be within: 1/50<N/M<200.

The electronic gear function provides easy travel distance ratio change. However, the over high electronic gear ratio will command the motor to move not smoothly. At this time, the users can use low- pass filter parameter to improve this kind of situation. For example, assume that the electronic gear ratio is equal to 1 and the encoder pulse per revolution is 10000ppr, if the electronic gear ratio is changed to 0.5, then the motor will rotate one pulse when the command from external controller is two pulses.

For example, after the proper electronic gear ratio is set, the reference travel distance is 1 μm/pulse, the machinery will become easier to be used.

6-8

Revision March 2008, Doc. Name: 2007PDD23000011

Page 111
Image 111