Chapter 7 Servo ParametersASDA-AB Series

P1 - 11

 

SP3

3rd Speed Command or Limit

Communication Addr.: 010BH

 

 

 

 

 

 

 

Default: 300

Related Section:

 

 

Applicable Control Mode: S, T

Section 6.3.1

Unit: r/min

Range: -5000 ~ +5000

Settings:

3rd Speed Command

In Speed mode, this parameter is used to set speed 3 of internal speed command. For the decimal place setting of internal speed command, please refer to P2-63.

3rd Speed Limit

In Torque mode, this parameter is used to set speed limit 3 of internal speed command.

P1 - 12

TQ1

1st Torque Command or Limit

Communication Addr.: 010CH

 

 

 

Default: 100

Related Section:

Applicable Control Mode: T, P/S

Section 6.4.1

Unit: %

 

 

Range: -300 ~ +300

Settings:

1st Torque Command

In Torque mode, this parameter is used to set torque 1 of internal torque command.

1st Torque Limit

In Position and Speed mode, this parameter is used to set torque limit 1 of internal torque command.

Digital output signal TQL is activated when the drive has detected that the motor has reached the torques limits set by either the parameters P1-12 ~ P1-14 of via an external analog voltage.