Chapter 7 Servo ParametersASDA-AB Series

P2 - 32▲

AUT2

Tuning Mode Selection

Communication Addr.: 0220H

 

 

 

Default: 0

 

Related Section:

Applicable Control Mode: ALL

Section 5.6, Section 6.3.6

Unit: N/A

 

 

Range: 0 ~ 5

Settings:

0: Manual mode

2:AutoMode (PI) [Continuous adjustment]

3:AutoMode (PI) [Fix the ratio of Load Inertia to servo motor inertia and response level can be adjusted]

4:AutoMode (PDFF) [Continuous adjustment]

5:AutoMode (PDFF) [Fix the ratio of Load Inertia to servo motor inertia and response level can be adjusted]

PI : Proportional - Integral control

PDFF : Pseudo-Derivative Feedback and Feedforward Explanation of Auto-tuning:

1.When switching mode #2 or #4 to #3, the system will save the measured load inertia value automatically and memorized in P1-37. Then, set the corresponding parameters according to this measured load inertia value.

2.When switching mode #2 or #4 to #0, it indicates all automatically measured load inertia value will be aborted, and all setting of parameters will be returned to original setting value in #0 manual mode.

3.When switching mode #0 to #3 or #5, enter the appropriate load inertia value in P1-37.

4.When switching mode #3 to #0, the setting value of P2-00, P2-04 and P2-06 will change to the value that measured in #3 auto-tuning mode.

5.When switching mode #5 to #0, the setting value of P2-00, P2-04, P2-06, P2-25 and P2-26 will change to the value that measured in #5 auto-tuning mode

7-62

Revision March 2008, Doc. Name: 2007PDD23000011