Chapter 3 Connections and WiringASDA-AB Series

 

 

 

 

 

 

 

Signal

Pin No

 

Details

Wiring Diagram

 

 

(Refer to 3-3-3)

 

 

 

 

 

 

 

 

 

14,29,

 

 

 

 

Other

NC

38,39,

See previous note for NC terminals CN1 connector

-

 

40,46,

on page 3-11.

 

 

 

 

 

 

 

 

 

48

 

 

 

 

 

 

 

 

 

 

 

The Digital Input (DI) and Digital Output (DO) have factory default settings which correspond to the various servo drive control modes. (See section 1.5). However, both the DI's and DO's can be programmed independently to meet the requirements of the users.

Detailed in Tables 3.B and 3.C are the DO and DI functions with their corresponding signal name and wiring schematic. The factory default settings of the DI and DO signals are detailed in Table 3.G and 3.H.

All of the DI's and DO's and their corresponding pin numbers are factory set and non-changeable, however, all of the assigned signals and control modes are user changeable. For Example, the factory default setting of DO5 (pins 28/27) can be assigned to DO1 (pins 7/6) and vise versa.

The following Tables 3.B and 3.C detail the functions, applicable operational modes, signal name and relevant wiring schematic of the default DI and DO signals.

Table 3.B DO Signals

DO

DO

Assigned

Pin No.

Details (*1)

Wiring Diagram

(Default)

Control

 

Signal

Code

Mode

 

 

 

(Refer to 3-3-3)

+

-

 

 

 

 

 

 

 

 

 

 

SRDY

01

ALL

7

6

SRDY is activated when the servo drive is

 

ready to run. All fault and alarm conditions, if

 

 

 

 

 

 

present, have been cleared.

 

 

 

 

 

 

 

 

 

 

 

 

 

SON is activated when control power is

 

 

 

 

 

 

applied the servo drive. The drive may or

 

 

 

 

 

 

may not be ready to run as a fault / alarm

 

 

 

 

 

 

condition may exist.

 

SON

02

Not

-

-

Servo ON (SON) is "ON" with control power

 

applied to the servo drive, there may be a

 

assigned

 

 

 

 

 

fault condition or not. The servo is not ready

 

 

 

 

 

 

 

 

 

 

 

 

to run. Servo ready (SRDY) is "ON" where

C5/C6/C7/C8

 

 

 

 

 

the servo is ready to run, NO fault / alarm

 

 

 

 

 

exists. (P2-51 should turn servo ready SRDY

 

 

 

 

 

 

off / on)

 

 

 

 

 

 

 

 

 

 

 

 

 

ZSPD is activated when the drive senses the

 

 

 

 

 

 

motor is equal to or below the Zero Speed

 

 

 

 

 

 

Range setting as defined in parameter P1-

 

ZSPD

03

ALL

5

4

38.

 

For Example, at factory default ZSPD will be

 

 

 

 

 

 

activated when the drive detects the motor

 

 

 

 

 

 

rotating at speed at or below 10 rpm. ZSPD

 

 

 

 

 

 

will remain activated until the motor speed

 

 

 

 

 

 

increases above 10 RPM.

 

Revision March 2008, Doc. Name: 2007PDD23000011

3-17