Chapter 10 TroubleshootingASDA-AB Series

 

 

: Watch dog execution time out

 

 

 

 

 

 

 

 

 

 

 

 

Potential Cause

Checking Method

Corrective Actions

 

 

 

 

If there are any abnormal

Watch dog execution

Check and reset the power supply.

conditions after resetting the power

supply, please contact your

error.

 

distributor for assistance or contact

 

 

 

 

 

 

 

 

with Delta.

 

 

 

 

 

: Encoder error (Position detector fault)

 

Potential Cause

 

 

Checking Method

Corrective Actions

The wiring of encoder is

 

1. Check if all wiring is correct.

Ensure all wiring is correct.

 

2.

Check if the users conduct the wiring by

in error.

 

 

the wiring information in the user manual.

 

 

 

 

 

 

 

 

 

 

 

 

 

Encoder is loose

 

Examine the encoder connector.

Install the motor again.

 

 

 

 

 

 

The wiring of encoder is

 

Check if all connections are tight.

Conduct the wiring again.

defective.

 

 

 

 

Encoder is damage

 

Check the encoder for the damage.

Repair or replace the motor.

 

 

: Adjustment error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Potential Cause

 

 

Checking Method

Corrective Actions

The setting value of

 

1.

Remove CN1 wiring.

If the error does not clear after

 

executing the drift adjustment

drift adjustment has

 

 

2. Execute the drift adjustment again. (Set

again, please contact your

exceeded its maximum

 

allowable value.

 

 

P2-08 to 20 first, and then set P4-10 to 5.)

distributor for assistance or contact

 

 

 

with Delta.

 

 

 

 

 

 

 

 

: Emergency stop activated

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Potential Cause

 

 

Checking Method

Corrective Actions

Emergency stop switch

 

Check if emergency stop switch is On or Off.

Activate emergency stop switch.

is activated.

 

 

 

 

 

 

: Reverse (CWL) limit switch error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Potential Cause

 

 

Checking Method

Corrective Actions

Reverse limit switch is

 

Check if reverse limit switch is On or Off.

Activate reverse limit switch.

activated.

 

 

 

 

 

 

 

 

 

Servo system is not

 

Check the value of control parameter setting

Modify parameter setting and re-

stable.

 

and load inertia.

estimate motor capacity.

 

 

: Forward (CCWL) limit switch error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Potential Cause

 

 

Checking Method

Corrective Actions

Forward limit switch is

 

Check if forward limit switch is On or Off.

Activate forward limit switch.

activated.

 

 

 

 

 

 

 

 

 

Servo system is not

 

Check the value of control parameter setting

Modify parameter setting and re-

stable.

 

and load inertia.

estimate motor capacity.

 

 

 

 

 

 

 

Revision March 2008, Doc. Name: 2007PDD23000011