Chapter 7 Servo ParametersASDA-AB Series

P4 - 05

JOG

JOG Operation

Communication Addr.: 0405H

 

 

 

Default: 20

Related Section:

Applicable Control Mode: ALL

Section 4.4.2

Unit: r/min

Range: 0~5000

Settings:

JOG operation command:

1.Operation Test

(1)Press the SET key to display the JOG speed. (The default value is 20 r/min).

(2)Press the UP or DOWN arrow keys to increase or decrease the desired JOG speed. (This also can be undertaken by using the SHIFT key to move the cursor to the desired unit column (the effected number will flash) then changed using the UP and DOWN arrow keys).

(3)Press the SET when the desired JOG speed is displayed. The Servo Drive will display "JOG".

(4)Press the UP or DOWN arrow keys to jog the motor either CCW or CW. The motor will only rotation while the arrow key is activated.

(5)To change JOG speed again, press the MODE key. The servo Drive will display "P4 - 05". Press the SET key and the JOG speed will displayed again. Refer back to #(2) and #(3) to change speed.

2.DI Signal Control

Set the value of DI signal as JOGU and JOGD (refer to Table 7.A). Users can perform JOG run forward and run reverse control.

3.Communication Control

To perform a JOG Operation via communication command, use communication address 0405H

(1)Enter 0 ~ 3000 for the desired JOG speed

(2)Enter 4998 to JOG in the CCW direction

(3)Enter 4999 to JOG in the CW direction

(4)Enter 5000 to stop the JOG operation

NOTE

1) If the communication write-in frequency is too high, please set P2-30 to 5.

7-82

Revision March 2008, Doc. Name: 2007PDD23000011