Chapter 3 Connections and WiringASDA-AB Series

NOTE

1)PINS 3 & 2 can either be TSPD or HOME dependent upon control mode selected.

2)PINS 1 & 26 are different depending on control mode either BRKR or TPOS.

Table 3.C DI Signals

DI

DI

Assigned

Pin No.

Details (*2)

Wiring Diagram

Control

 

 

 

Signal

Code

Mode

(Default)

 

(Refer to 3-3-3)

 

 

 

 

 

 

 

 

 

 

 

SON

01

ALL

9

Servo On. Switch servo to "Servo Ready".

 

Check parameter P2-51.

 

 

 

 

 

 

 

 

 

 

A number of Faults (Alarms) can be

 

 

 

 

 

cleared by activating ARST. Please see

 

 

 

 

 

table 10-3 for applicable faults that can be

 

ARST

02

ALL

33

cleared with the ARST command.

 

However, please investigate Fault or

 

 

 

 

 

 

 

 

 

 

Alarm if it does not clear or the fault

 

 

 

 

 

description warrants closer inspection of

 

 

 

 

 

the drive system.

 

GAINUP

03

ALL

-

Gain switching

 

 

 

 

 

 

 

 

 

 

 

When CCLR is activated the setting is

 

CCLR

04

Pt

10

parameter P2-50 Pulse Clear Mode is

 

 

 

 

 

executed.

 

 

 

 

 

 

 

 

 

 

 

When this signal is On and the motor

 

ZCLAMP

05

ALL

-

speed value is lower than the setting value

 

of P1-38, it is used to lock the motor in the

 

 

 

 

 

 

 

 

 

 

instant position while ZCLAMP is On.

 

 

 

 

 

 

 

CMDINV

06

Pr, T, S

-

When this signal is On, the motor is in

 

reverse rotation.

 

 

 

 

 

C9/C10

 

 

 

 

 

HOLD

07

Not

 

Internal position control command pause

 

 

assigned

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When the drive is in Pr mode and CTRG is

 

 

 

Pr,

 

activated, the drive will command the

 

CTRG

08

10

motor to move the stored position which

 

Pr-S, Pr-T

correspond the POS 0, POS 1, POS 2

 

 

 

 

 

 

 

 

 

settings. Activation is triggered on the

 

 

 

 

 

rising edge of the pulse.

 

 

 

 

 

 

 

TRQLM

09

S, Sz

10

ON indicates the torque limit command is

 

valid.

 

 

 

 

 

 

SPDLM

10

T, Tz

10

ON indicates the speed limit command is

 

valid.

 

 

 

 

 

 

 

 

 

 

 

 

POS0

11

Pr

34

When the Pr Control Mode is selected the

 

 

 

 

 

 

 

 

 

 

8 stored positions are programmed via a

 

POS1

12

Pr-S, Pr-T

8

 

combination of the POS 0, POS 1, and

 

 

 

 

 

 

POS2

13

-

-

POS 2 commands. See table 3.D.

 

 

 

 

 

 

 

 

 

SPD0

14

S, Sz, Pt-S,

34

Select the source of speed command:

 

 

 

 

 

SPD1

15

Pr-S, S-T

8

See table 3.E.

 

 

 

 

 

 

 

 

 

 

Revision March 2008, Doc. Name: 2007PDD23000011