Delta Electronics none manual Tspd ALL, Tpos, Tql, Alrm ALL, Brkr ALL, Home, Olw All, Warn ALL

Models: none

1 355
Download 355 pages 2.82 Kb
Page 45
Image 45

Chapter 3 Connections and WiringASDA-AB Series

DO

DO

Assigned

Pin No.

Details (*1)

Wiring Diagram

(Default)

Control

 

Signal

Code

Mode

 

 

 

(Refer to 3-3-3)

+

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TSPD is activated once the drive has

 

 

 

 

 

 

detected the motor has reached the Target

 

TSPD

04

ALL

3

2

Rotation Speed setting as defined in

 

parameter P1-39. TSPD will remain activated

 

 

 

 

 

 

 

 

 

 

 

 

until the motor speed drops below the Target

 

 

 

 

 

 

Rotation Speed.

 

 

 

 

 

 

 

 

 

 

 

 

 

1. When the drive is in Pt mode, TPOS will

 

 

 

 

 

 

be activated when the position error is

 

 

 

 

 

 

equal and below the setting value of P1-

 

 

 

 

 

 

54.

 

 

 

Pt, Pr, Pt-

 

 

2. When the drive is in Pr mode, TPOS will

 

 

 

 

 

be activated when the drive detects that

 

 

 

S,

 

 

 

TPOS

05

1

26

the position of the motor is in a -P1-54 to

 

Pt-T, Pr-S,

 

 

 

 

 

+P1-54 band of the target position. For

 

 

 

Pr-T

 

 

 

 

 

 

 

Example, at factory default TPOS will

 

 

 

 

 

 

 

 

 

 

 

 

activate once the motor is in -99 pulses

 

 

 

 

 

 

range of the target position, then

 

 

 

 

 

 

deactivate after it reaches +99 pulses

 

 

 

 

 

 

range of the desired position.

 

 

 

 

 

 

TQL is activated when the drive has detected

 

TQL

06

Not

-

-

that the motor has reached the torques limits

 

assigned

set by either the parameters P1-12 ~ P1-14

 

 

 

 

 

 

 

 

 

 

 

of via an external analog voltage.

 

 

 

 

 

 

 

 

 

 

 

 

 

ALRM is activated when the drive has

 

 

 

 

 

 

detected a fault condition. (However, when

 

ALRM

07

ALL

28

27

Reverse limit error, Forward limit error,

C5/C6/C7/C8

Emergency stop, Serial communication error,

 

 

 

 

 

and Undervoltage these fault occur, WARN

 

 

 

 

 

 

is activated first.)

 

BRKR

08

ALL

1

26

BRKR is activated actuation of motor brake.

 

 

 

 

 

 

 

 

 

 

 

 

 

HOME is activated when the servo drive has

 

 

 

 

 

 

detected that the "HOME" sensor (Digital

 

HOME

09

Pt, Pr

3

2

Input 24) has been detected and the home

 

 

 

 

 

 

conditions set in parameters P1-47, P1-50,

 

 

 

 

 

 

and P1-51 have been satisfied.

 

 

 

 

 

 

 

 

 

 

 

 

 

OLW is activated when the servo drive has

 

OLW

10

ALL

-

-

detected that the motor has reached the

 

output overload level set by the parameter

 

 

 

 

 

 

 

 

 

 

 

 

P1-56.

 

 

 

 

 

 

 

 

 

 

 

 

 

Servo warning output. WARN is activated

 

 

 

 

 

 

when the drive has detected Reverse limit

 

WARN

11

ALL

-

-

error, Forward limit error, Emergency stop,

 

 

 

 

 

 

Serial communication error, and

 

 

 

 

 

 

Undervoltage these fault conditions.

 

 

 

 

 

 

 

 

 

 

 

 

 

Internal position command completed output.

 

 

 

 

 

 

CMDOK is activated when the servo drive

 

CMDOK

12

ALL

-

-

has detected that the internal position

 

command has been completed or stopped

 

 

 

 

 

 

 

 

 

 

 

 

after the delay time which is set by the

 

 

 

 

 

 

parameter P1-62 has elapsed.

 

Footnote *1: The "state" of the output function may be turned ON or OFF as it will be dependant on the settings of P2-18~P2-22.

3-18

Revision March 2008, Doc. Name: 2007PDD23000011

Page 45