Teledyne gfc 7000ta operation manual Current Loop Output Adjustment, Edit

Models: gfc 7000ta

1 280
Download 280 pages 4.46 Kb
Page 149
Image 149

Operating Instructions

Model GFC7000TA Carbon Dioxide Analyzer

FROM ANALOG I/O CONFIGURATION MENU

DIAG

ANALOG I / O CONFIGURATION

PREV NEXT

 

ENTR EXIT

 

 

 

 

DIAG AIO

AOUTS CALIBRATED: NO

< SET SET>

CAL

 

EXIT

 

Press SET> to select the analog output channel to be

 

 

configured:

 

 

 

DISPLAYED AS=

CHANNEL

 

CONC_OUT_1 =

A1

 

 

CONC_OUT_2 =

A2

 

TEST OUTPUT =

A4

 

 

DIAG AIO

CONC_OUT_1 :5V, NO CAL

< SET SET>

EDIT

 

EXIT

 

 

 

 

 

Press to increase / decrease the analog output

by 100, 10 or 1 counts.

Continue adjustments until the voltage measured at the output of the analyzer and/or the input of the recording device matches the value in the upper right hand corner of the display to the tolerance listed in Table 6-20.

The concentration display will not change. Only the voltage reading of your voltmeter will change.

DIAG AIO

 

 

CONC_OUT_1

RANGE: 5V

 

 

 

 

SET>

EDIT

 

 

EXIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DIAG AIO

 

 

CONC_OUT_1 REC OFS: 0 mV

 

< SET SET> EDIT

 

 

EXIT

 

 

 

 

 

DIAG AIO CONC_OUT_1 AUTO CAL: OFF

 

 

 

< SET SET>

EDIT

 

 

EXIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DIAG AIO

 

CONC_OUT_2 CALIBRATED: NO

 

 

< SET

CAL

 

 

 

EXIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DIAG AIO

CONC_OUT_1 VOLT–Z : 0 mV

 

 

 

U100

 

UP10

UP DOWN

DN10 D100 ENTR EXIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DIAG AIO

CONC_OUT_1 VOLT–S : 4500 mV

 

 

U100

UP10 UP DOWN

DN10 D100 ENTR EXIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DIAG AIO CONC_OUT_1 CALIBRATED: YES

 

 

< SET

CAL

 

 

EXIT

 

 

 

 

 

 

 

 

 

 

 

 

If AutoCal is ON, go to

Section 6.7.3

EXIT ignores the new setting.

ENTR accepts the new setting.

6.13.4.4. Current Loop Output Adjustment

A current loop option is available and can be installed as a retrofit for each of the analog outputs of the analyzer (s 5.2). This option converts the DC voltage analog output to a current signal with 0-20 mA output current. The outputs can be scaled to any set of limits within that 0-20 mA range. However, most current loop applications call for either 2-20 mA or 4-20 mA range. All current loop outputs have a +5% over-range. Ranges with the lower limit set to more than 1 mA (e.g., 2-20 or 4-20 mA) also have a -5% under-range.

To switch an analog output from voltage to current loop after installing the current output printed circuit assembly, follow the instructions in Section 6.13.4.4 and select CURR from the list of options on the RANGE menu.

Adjusting the signal zero and span values of the current loop output is done by raising or lowering the voltage of the respective analog output. This proportionally raises or lowers the current produced by the current loop option.

Similar to the voltage calibration, the software allows this current adjustment to be made in 100, 10 or 1 count increments. Since the exact current increment per voltage count varies from output to output and from instrument to instrument, you will need to measure the change in the current with a current meter placed in series with the output circuit (Figure 6-16).

Teledyne Analytical Instruments

131

Page 149
Image 149
Teledyne gfc 7000ta operation manual Current Loop Output Adjustment, Edit