11-4 Alarm Ports
Model No.
Running Head
Alarm port User Screens and Settings Alarm ports
Table 11-1. Alarm Contacts Main Screen Actions
Table 11-2. Alarm Contacts Settings and Defaults
SWITCH
The Switch setting indicates that the outbound alarm switch is actv (on) or stdby (off).
ACT ON
The Act On parameter defines the type of sys tem alarm that will cause the switch to trigg e r.
Program each alarm switch to trigger on minor (information and minor) alarms, major (major
and critical) alarms, or any alarm message.
SENSOR
The Sensor setting indicates the inbound alarm sensor is actv (on) or stdby (off).
TRIG ON
The Trigger On parameter defines if the sensor should report an external al arm upon sensing
the opening (open) or the closure (close) of the external contact to which it is connected.
Action Function
Save Saves changes to settings.
Undo Returns all settings to the last saved state.
Refresh Updates certain time-related information fields that are not automatically
updated on screen (i.e., alarm data).
Main Returns to the System Main Screen. If changes are made to settings and
not saved, you will be prompted to save or lose changes.
Parameter User Options Default
SWITCH stdby actv stdby
ACT ON minor major any minor
SENSOR stdby actv stdby
TRIG ON close open close