4 |
memory type is %R, this is the number of words. A maximum of 16384 bits/2048 bytes/1024 words of data may be specified.
(Word 18) Remote PLC - PLC (Node) Address Type: Word 18 specifies the format of the remote PLC address. In this release, Word 18 must contain the value one (1), indicating a
(Word 19) Remote PLC - PLC (Node) Address Length: Word 19 specifies the length in words of the remote PLC IP address. In this release Word 19 must contain four (4).
(Words
Words 24 - 27 Remote PLC - Program Name: Word 24 - 27 specify the
Word 28 - 31 Remote PLC - Program Block Name: Words 28 - 31 specify the case- sensitive,
Note
The Program Name (words 24 - 27) and Program Block Name (words
28 - 31) must have each pair of ASCII characters reversed within the PLC memory. For example, the name ªMARYº (ªMº = 4DH, ªAº = 41H, ªRº = 52H, ªYº = 59H) would have 414D in the first word and 5952 in the second word.
TCP/IP Ethernet Communications User's Manual ± January 1996 |
|