5 |
SOSW Command
(Not recommended if the PLC CPU is configured properly.)
This command displays the current setting of the Ethernet Interface Soft Switches or a message indicating that no Soft Switch values are defined. If not defined, the operator must set Soft Switch values, using the CHSOSW command, before the Ethernet Interface can proceed to any state beyond the Soft Switch Entry utility.
The command output is different depending upon the Logicmaster configuration mode (TCP/IP or
SOSW
A typical
> sosw
<<<Soft Switch Data >>>
Config Mode:
MAC address = <<080019010177>> (Using default) Load source = Serial
Network Online = Online after powerup Backplane Online = Online after powerup Networkload addr = <<090060000000>> (using default) MMS Enable = Don't care *
Pgmr Enable = Don't care Source of Soft Switches: CPU
* Unused by the TCP/IP Ethernet Interface.
Also displayed is the source, CPU or Internal Backup, of the Soft Switch data.
STAT Command
The STAT command has the form:
STAT <task(s)>
where <task(s)> is one or more task identification letters from Table
This command causes the current status of the task or tasks specified by the task identifi- cation letters to be displayed. An example STAT command is shown below:
= stat i
<<< IP Status >>>
Local IP Addr = 3.16.16.18, Subnet Mask = 255.255.252.0
Gateway Addr = 3.16.19.240
TCP/IP Ethernet Communications User's Manual ± January 1996 |
|