2

3.Clear the error log and LLC and MAC tallies in all GE Fanuc test responders in the test. This step cannot be performed for non±GE Fanuc devices using the Station Manager.

This step can be done for all Ethernet Interfaces at one time by executing the following REMote commands:

$

rem 010000000000

login system

:

Logon to all GE Fanuc stations

$

rem

010000000000

clear

log

:

Clear logs of all GE Fanuc stations

$

rem

010000000000

clear

tally

:

Clear tallies of all GE Fanuc stations

Note

Pressing Ctrl±Rwill display the last command executed. This is especially helpful when you are repeating similar commands. Simply display the previous command, change the desired part of the command, and press Enter.

This step can be done for individual Ethernet Interfaces by executing the following set of

REMote commands for each Ethernet Interface to be tested.

$ rem <node> login system $ rem <node> clear log

$ rem <node> clear tally

where <node> is the 12±digit MAC address of the target node.

4.To clear the error log and LLC and MAC tallies in the test initiator Ethernet Interface, issue the following commands:

$ clear log

$ clear tally

5.Issue the desired TEST command to initiate the network test.

$

test

010000000000 1000 50 256

:Tests all GE Fanuc stations on the

 

 

 

network

or

 

 

 

$

test

all 1000 50 256

:Tests all stations on the network

The TEST command causes the test initiator to broadcast 1000 test command frames of varying lengths and data patterns to all GE Fanuc nodes or all nodes of all types on the network. All nodes receiving these commands are expected to send a similar test response back to the initiating node. The initiating node counts all responses from each responding node.

This command will take about 10 minutes to complete. When the command is com- plete, a report like the following should be displayed.

<<< Test Results >>>

 

 

Page 1 of 1

Command: test

<<ffffffffffff>>

3e8H 32H

100H ALT

 

Init Node: <<08001901001f>> Frames

sent: 3e8H Nodes responding: 4H

Responding nodes

Response recd

Response w/err

No Response

<<08001901027d>>

3e8H

0H

 

0H

<<080019010163>>

3e8H

0H

 

0H

<<080019010043>>

3e8H

0H

 

0H

<<08001901012c>>

3e8H

0H

 

0H

GFK-1004B

Chapter 2 Installing the Ethernet Interface

2-27

Page 48
Image 48
GE GFK-1004B user manual Issue the desired Test command to initiate the network test