C

Modify Soft Switch Settings

Refer to the table below for the default Soft Switch settings and Soft Switch modification information.

Table C-1. Soft Switch Settings

Parameter

Description

 

 

Station Address

The station address parameter is the Medium AccessControl(MAC) address of the

 

station being configured. The MAC address is a 12-digit hexadecimalnumber

 

which is organized as 6 bytes, each represented by a pair of hexadecimaldigits.

 

DefaultSetting - The default value is <<000000000000>> . This value instructs the

 

Ethernet Interface to use the factory-set,globally-uniqueMAC address in its EEPROM.

 

ModificationfromDefaultSetting - If changed, the Ethernet Interface will store the

 

new Station Address in the EEPROM and use it instead of the factorydefault.

LoadSource

The load source field defines the load source for the GEnet LAN software.

 

DefaultSetting - The default setting for this field is ªALTº. This means that the

 

 

Ethernet Interface module will try to obtain a load from the serial port and the

 

network (in that order). The software will alternate between the two load sources

 

until one is found.

 

ModificationfromDefaultSetting - You may wish to specify the load source. The load

 

source may be changed to:

 

ªLOCº (serial port) - only

 

ªNETº (network) - only

 

If the load source specified is not available for the module, it will wait indefinitely for

 

that load source to be made available.

LANOnline

This parameter tells the GEnet LAN Interface module whether to connect to the LAN

 

afterinitialization.

 

DefaultSetting - The default setting is YES. This means that the module will

 

connect to the LAN.

 

ModificationfromDefaultSetting - The default may be changed to NO. This

 

 

means that the module will not connect to the LAN.

BackplaneOn-

This parameter tells the GEnet LAN Interface module whether or not to allow back-

line

planecommunications.

 

DefaultSetting - The default setting is YES. This means that the module will allow

 

all formsofbackplanecommunications.

 

ModificationfromDefaultSetting - The default may be changed to NO. This

 

means that the module will only allow diagnostics mail traffic. This setting will not

 

permit application data transfer with the Series 90-70 CPU.

NetworkLoad

The multicast address to be used by the LAN Interface to load across the LAN. It is in

Address

the same format as the Station Address.

 

DefaultSetting - The default value is <<000000000000>> . This value instructs the

 

LANInterface to use the default network load address, <<090060000000>> , as its

 

loadaddress.

 

ModificationfromDefaultSetting - If changed the Ethernet Interface will look for a

 

network load from the specified multicast address. This MUST be a multicast address.

C-4

TCP/IP Ethernet Communications User's Manual ± January 1996

GFK-1004B