6.Text similar to that shown below will be displayed on the terminal after the diagnostics are run. The Soft Switch Entry Utility banner will appear only if the Ethernet Interface is in the Soft Switch Entry state. The CHSOSW command may be used in any of the Ethernet Interface states.

IC697 PLC Factory LAN Interface

Copyright (c) 1990-1995. All rights reserved

PROM version 2.00 (xxAx) Ethernet

IP address = 3.16.18.47

MAC address = <<08001901001f>> MAC default = <<08001901001f>>

EM7A2

<<<Soft Switch Entry Utility >>>

7.A ª*º or other prompt character will be displayed on the terminal.

8.To display the current values of the Soft Switches, enter the command SOSW.

9.Set the values of the Soft Switches by entering the CHSOSW command. (Refer to Chapter 4, Station Manager, for a detailed definition of the command syntax.)

The new values of the Soft Switches will be displayed. A typical CHSOSW command for the Ethernet Interface is shown below:

*chsosw mac 020106000001 mms dc

<<< Soft Switch Data >>>

Config. Mode: MMS-ETHERNET

MAC Address = <<08001901001f>> (default used) Load source = Serial

Network Online

=

Online

after

power

up

Backplane Online =

Online

after

power

up

Network doad addr = <<090060000000>> (default used)

MMS Enable = Don't Care *

Pgmr Enable = Don't Care *

Source of Soft Switches: Internal Backup

Updating, please wait ...

*Not used by the TCP/IP Ethernet Interface.

10.If the Soft Switch data displayed in the CHSOSW command is correct for the station, press the LAN Interface Restart button to cause the new Soft Switch values to take effect. If the values shown are not what you want, repeat step 10, supplying the proper values.

Caution

Soft switch values set by the CHSOSWStation Manager command will be overridden by values configured in the Logicmaster 90-70 Configurator.

C-6

TCP/IP Ethernet Communications User's Manual ± January 1996

GFK-1004B

Page 226
Image 226
GE GFK-1004B user manual Soft Switch Entry Utility