Table 6-10. Exception Log Event Codes - Continued

Log Event

Code

Eventª2º System events (Continued)

Possible Cause and Resolution

System Error: 03

ªLANPROM/softwaremismatch;running soft Sw utilº

This error indicates that an outdated configuration data file has been loaded into the Ethernet Interface along with the software. Entry 3 indicates the lowest required configuration data file version for the software; Entry 4 indicates the actual loaded configuration data version. Check that the proper configuration data file is being downloaded by the GSM. If the Ethernet Interface software, or the GSM itself, has been recently upgraded, it may be necessary to update the configuration data file for this station. This fault causes entry into the Soft Switch Entry Utility.

System Error: 04

ªLANPROM/softwaremismatch;running soft Sw utilº

This error indicates that an improper configuration file has been loaded for this station. The MAC address within the configuration file does not match the MAC address supplied by the Soft Switches. The system cannot initialize with an improper configuration file. Check that the proper MAC address is set in the Soft Switches. Also check that the station is configured with the proper MAC address in the GSM, and that the proper configuration file is being downloaded by the GSM. Entries 3, 4, and 5 indicate the 12-digit MAC address obtained from the configuration file. The MAC address obtained from Soft Switches may be displayed with the NODE and SOSW Station Manager commands. This fault causes entry into the Soft Switch EntryUtility.

System Error: 08

(Not reported to CPU Fault Table)

Soft Switch values are not defined. This fault causes entry to the Soft Switch EntryUtility. Entry 3 distinguishes the reason for reporting Soft Switches not defined:

0CLSOSWStation Manager command was issued.

1EEPROM checksum was incorrect.

System Error: 09

ªLANsystem-softwarefault;resumingº

Unable to set the Ethernet Interface date and time to the same values as the PLC CPU. This error may occur at system startup. The Ethernet Interface time and date are initialized to 00:00:00, 01-JAN-1989. Entry 3 indicates the reason for this error:

0Unable to retrieve information from the PLC CPU. This errorwill occur if the Ethernet Interface is not configured in the PLC CPU via the LM90 Configuration Software.

1Invalid date/time value retrieved from the PLC CPU. The Ethernet Interface cannot accept dates prior to 01-JAN-1989. Check that the current date and time are established in the PLC CPU via the LM90 ConfigurationSoftware.

6-12

TCP/IP Ethernet Communications User's Manual ± January 1996

GFK-1004B

Page 183
Image 183
GE GFK-1004B user manual Log Event Code