The Power-Up State
When power is cycled on the Series
Note
TheRestart/LoadPushbutton is not operable during the Ethernet
Interface diagnostic phase nor is the Station Manager active. The
Ethernet Interface is in diagnostic phase when the MODULE OK LED is
BLINKING and the ONLINE and STATUS OK LEDs remain OFF.
After diagnostics complete, both the MODULE OK LED and STATUS OK LED blink slowly for
Table 6-2. Power-Up State
| Running | Wait for Field | Wait for PLC & | Diagnostic | |
LED | Diagnostics | Network Test | CPU Handshake | ||
Failed | |||||
| (15 sec) | (to 60 sec) | |||
|
| ||||
|
|
|
|
| |
MODULE OK | Blink | Slow Blink | Slow Blink | OFF | |
ONLINE | OFF | OFF | OFF | OFF | |
STATUS OK | OFF | Slow Blink | OFF | OFF | |
The PLC Fault Table can be especially helpful in detailing faults that are detected in the
Note
If all LEDs go out after completing
The Soft Switch Entry State
The Soft Switch Entry State is indicated by the MODULE OK LED blinking slowly (every 2 seconds) while the other LEDs remain OFF. The Soft Switch Entry state is automatically entered when the Soft Switch data in the Ethernet Interface is invalid and has not been set up by the Logicmaster