![](/images/new-backgrounds/1187338/187338369x1.webp)
6 |
Table 6-10. Exception Log Event Codes - Continued
Log Event |
|
Code | Possible Cause and Resolution |
Event ª2º | System Error: 3e7 |
System events | |
(Continued) | This error is caused by a request to release a buffer which is either still on a |
| queue or not on an even boundary. This is a catastrophic system software |
| error and should be reported to GE Fanuc - NA. The Ethernet Interface is |
| automatically restarted. If this error occurs within the first 60 seconds after |
| the Ethernet Interface was restarted or power cycled, the automatic restart |
| will force the Ethernet Interface into the Soft Switch EntryUtility. |
| System Error: bbbb |
| ªLowbatterysignalº |
| This error occurs when the battery is disconnected or running low. Entry 3 |
| indicates what type of transition has occurred: |
| 0 Battery went from good to bad. |
| 1 Battery went from bad to good (does not cause the STATUS LED to go |
| OFF). |
| System Error: cccc |
| ªModulehardwarefaultº |
| This error occurs when the system detects an incorrect checksum in the |
| software or configuration data loaded into memory. This is a catastrophic |
| error. The Ethernet Interface is restarted with entry into the Software Load |
| Utility. |
| Entry 3 indicates the correctchecksumvalue. |
| Entry 4 indicates the actual computed value. |
| Entry 5 indicates the internal range number within the software; range 0 |
| indicates an error within the configuration data; Range ee indicates an |
| error within the copy of EEPROM data. Occurrence of this error should be |
| reported to GE Fanuc - NA. |
TCP/IP Ethernet Communications User's Manual ± January 1996 |
|