GE GFK-1004B user manual System Error cccc

Models: GFK-1004B

1 268
Download 268 pages 52.5 Kb
Page 185
Image 185

6

Table 6-10. Exception Log Event Codes - Continued

Log Event

 

Code

Possible Cause and Resolution

Event ª2º

System Error: 3e7

System events

ªLANI/Fcan'tinit-checkparms; running soft Sw utilº

(Continued)

This error is caused by a request to release a buffer which is either still on a

 

queue or not on an even boundary. This is a catastrophic system software

 

error and should be reported to GE Fanuc - NA. The Ethernet Interface is

 

automatically restarted. If this error occurs within the first 60 seconds after

 

the Ethernet Interface was restarted or power cycled, the automatic restart

 

will force the Ethernet Interface into the Soft Switch EntryUtility.

 

System Error: bbbb

 

ªLowbatterysignalº

 

This error occurs when the battery is disconnected or running low. Entry 3

 

indicates what type of transition has occurred:

 

0 Battery went from good to bad.

 

1 Battery went from bad to good (does not cause the STATUS LED to go

 

OFF).

 

System Error: cccc

 

ªModulehardwarefaultº

 

This error occurs when the system detects an incorrect checksum in the

 

software or configuration data loaded into memory. This is a catastrophic

 

error. The Ethernet Interface is restarted with entry into the Software Load

 

Utility.

 

Entry 3 indicates the correctchecksumvalue.

 

Entry 4 indicates the actual computed value.

 

Entry 5 indicates the internal range number within the software; range 0

 

indicates an error within the configuration data; Range ee indicates an

 

error within the copy of EEPROM data. Occurrence of this error should be

 

reported to GE Fanuc - NA.

6-14

TCP/IP Ethernet Communications User's Manual ± January 1996

GFK-1004B

Page 185
Image 185
GE GFK-1004B user manual System Error cccc