2

Invoking the Field Network Test Utility

To invoke the Field Network Test Utility you need to connect the GSM locally to one of the Ethernet Interfaces on the network.

HRefer to Chapter 3, ªThe GEnet System Managerº, for instructions on installing the GSM software on a user supplied WorkmasterorIBM±PCCompatiblecomputer.

HSeeInstallationProcedure 2 in this chapter for instructions on using the terminal emulation feature of the GSM.

Note

Alternately, you can use a dumb terminal, or another terminal emulation product on a PC. However, you will probably find it most convenient to use the GSM terminal emulation feature since you will be using the GSM for other configuration purposes. Configure the terminal for 9600 bps, 8 bits, no parity, and 1 stop bit.

Perform the following steps to invoke the Field Network Test Utility.

1.Connect the GSM locally to one of the Ethernet Interfaces on the Network you are testing.

2.Power up the PLC (if power is already on, you need to cycle power or press the Restart push±button on the Ethernet Interface ).

3.After step 7 of the power±up diagnostic is complete, the ª@º symbol will appear on the terminal device. After the ª@º symbol appears, you have 3 seconds to enter the single character (ªFº or ªfº) to invoke the Field Network Test Utility. The ªFº will not be echoed back. Any characters other than ªfº or ªFº are ignored. If you do not see a startup message displayed like the one shown below, press the Restart button on the Ethernet Interface (or cycle power on the station) and repeat this step.

The expected startup message upon entering the Field Network Test Utility is similar to the one shown here:

@

IC697 PLC Factory LAN Interface

Copyright (c) 1990-1995. All rights reserved. PROM Version 2.00 (xxAn)

MAC address = <<08001901001f>>, MAC default = <<08001901001f>> EM7A2

<<<Field Network Test Utility >>>

$

4.Repeat steps 1 through 3 for each Ethernet Interface to be tested.

GFK-1004B

Chapter 2 Installing the Ethernet Interface

2-25

Page 46
Image 46
GE GFK-1004B user manual Invoking the Field Network Test Utility