Honeywell UDC 3300 manual Relhum, Summer with Ratio and BIAS- The following

Models: UDC 3300

1 294
Download 294 pages 16.21 Kb
Page 109
Image 109

Lower Display

Prompt

Upper Display

 

 

Parameter

Range of Setting

 

 

Definition

or Selection

 

 

 

 

 

 

 

FFWDMu

 

FEEDFORWARD MULTIPLIER— Feedforward uses Input

 

 

A, following a Ratio and Bias calculation as a value

 

 

multiplied directly with the PID computed output value and

 

 

sent, as an output value, to the final control element.

 

 

(NOTE 1)

 

 

The following formula applies:

 

 

 

 

Controller Output = PID Output x (Input A x Ratio A + Bias A )/Input A Range

RELHUM

 

RELATIVE HUMIDITY— Input 1 reads the wet bulb

 

 

temperature. Input 2 reads the dry bulb temperature. Both

 

 

inputs must be 100 ohm RTD inputs.

 

 

 

 

 

 

ATTENTION

The Relative Humidity selection will

 

 

automatically force both Analog Input actuations to the

 

 

100 ohm low setting.

 

 

The controller will indicate measured Relative Humidity as

 

 

a Process Variable (PV) with a setpoint range of 0 % to

 

 

100 % RH.

 

 

 

SUMMER

 

SUMMER WITH RATIO AND BIAS— The following

 

 

formula applies:

 

 

PV = (Input A x Ratio A + Bias A) + (Input B x Ratio B + Bias B) + (Input C x Ratio C + Bias C)

 

 

 

HI SEL

 

INPUT HIGH SELECT WITH RATIO AND BIAS— This

 

 

selection specifies the PV or SP as the higher of Input 1 or

 

 

Input 2. The following formula applies:

 

 

 

 

PV = higher of (Input A x Ratio A + Bias A) or (Input B x Ratio B + Bias B)

LO SEL

INPUT LOW SELECT WITH RATIO AND BIAS—This selection specifies the PV or SP as the lower of Input 1 or Input 2. The following formula applies:

PV = lower of (Input A x Ratio A + Bias A) or (Input B x Ratio B + Bias B)

MuDIV (note 2)

MULTIPLIER DIVIDER WITH SQUARE ROOT— The following formula applies:

 

(Input A x Ratio A + Bias A) x (Input C x Ratio C + Bias C)

*PV = K x

 

x (Calc Hi – Calc Lo)

 

 

(Input B x Ratio B + Bias B)

See Figure 4-1 at the end of this section for an example of Mass Flow Compensation using Multiplier/Divider Algorithm.

MULT (note 2)

MULTIPLIER WITH SQUARE ROOT— The following

formula applies:

*PV = K x (Input A x Ratio A + Bias A) x (Input C x Ratio C + Bias C) x (Input B x Ratio B + Bias B) x (Calc Hi – Calc Lo)

MuDIV

MULTIPLIER DIVIDER—The following formula applies:

*PV = K x

(Input A x Ratio A + Bias A) x (Input C x Ratio C + Bias C)

 

x (Calc Hi – Calc Lo)

 

 

(Input B x Ratio B + Bias B)

MULT

MULTIPLIER— The following formula applies:

*PV = K x [(Input A x Ratio A + Bias A) x (Input C x Ratio C + Bias C) x (Input B x Ratio B + Bias B)] x (Calc Hi – Calc Lo)

CARB A

CARBON POTENTIAL A— Make this selection if you have a Cambridge or Marathon monitor type Zirconium Oxide sensor.

4/00

UDC 3300 Process Controller Product Manual

97

Page 109
Image 109
Honeywell UDC 3300 manual Relhum, Summer with Ratio and BIAS- The following, Input High Select with Ratio and BIAS- This