Thermocouple inputs using a precision resistor

Referring to Figure 7-3, wire the controller according to the procedure given in Table 7-4.

Table 7-4 Set Up Wiring Procedure for Thermocouple Inputs

Using a Precision Resistor

Step

1

2

3

4

Action

Connect the copper leads to the calibrator.

Disconnect the cold junction resistor.

Install a 500-ohm precision resistor across Input 1 terminals 25 (R) and 27 (–) or Input 2 terminals 22 (R) and 24 (–). See Figure 7-3.

Subtract the millivolt value for 77 °F (25 °C) from the zero and span value for your range (see Table 7-1 for zero and span values) and use the adjusted value when calibrating.

Figure 7-3 Wiring Connections for Thermocouple Inputs

Using a Precision Resistor

 

 

 

10

1

 

 

L1

11

2

 

R

L2/N

12

3

 

22

13

4

 

+

 

23

14

5

Input 2

 

 

 

 

 

 

 

 

 

24

15

6

 

R

25

16

7

 

+

 

26

17

8

 

Input 1

27

 

9

 

 

Copper Leads Precision 500 Ohm Resistor 1

+

Millivolt Source

1Caution: The accuracy of the controller is directly affected by the accuracy of this resistor. At a minimum, use a 0.1%, 25ppm resistor.