Description

Configuration

The “AM STA” selection of digital input creates a repeater station when the digital input is closed. This is accomplished by a multi-selection from the digital input menu.

“ACTION” is forced as “DIRECT”.

“CONT ALG” is forced as “PD+MR”.

Active setpoint is forced to 2SP.

The PV is switched to “PV 2IN”.

The tuning parameters used are the second set of parameters.

When the switch is open the unit becomes a normal controller with “CONT ALG” of “PID A”, using tuning parameters set 1, SP, PV as IN1 and “DIRECT” or “REVERSE” as selected by customer configuration.

Input 1 is typically the PV of some upper controller and Input 2 is typically that controller’s output. If the upper control fails, the upper device or some watchdog opens the digital input switch and UDC 3300 back-up PID A control is active.

When the upper control reactivates, the digital input switch is closed and the Auto/Manual Station becomes a repeater station and allows the upper control output signal to pass through.

There are some things to consider when configuring the controller.

The PV range stays as the IN1 range, even while IN2 is the PV when the switch is closed; therefore:

The IN2 HI must be less than or equal to the IN1 HI. (Suggest: IN2 HI = 100.0)

The IN2 LO must be greater than or equal to the IN1 LO. (Suggest: IN2 LO = 0.0)

The TUNING GAIN2 must be equal to (IN1 HI – IN1 LO) / (IN2 HI – IN2 LO).

Configuration

Refer to Table 5-33 and set up the controller in the order shown.

Table 5-33 Auto/Manual Station Mode Configuration Procedure

Step

1

2

3

 

 

 

 

 

 

Press

SET

 

Press

FUNC

to

UP

 

 

 

 

 

 

to Select Set

Select

 

Up Group

Function

 

 

 

 

Prompts

 

 

 

 

Control

PID SETS

 

 

 

 

LSP’S

 

 

 

 

SP TRACK

 

Algorithm

CONT ALG

 

Tuning

MAN RSET

 

 

 

 

 

 

 

Press ▲ ▼

 

to Enter

Remarks

Value or

 

Selection

 

 

 

2KEYBD

Select other control parameters as needed by the

TWO

application.

 

NONE

 

PD+MR

This allows setting of the Manual Reset value.

0Manual reset of 0 for no output bias and requires LSP2 = 0 %. If bias is required, set MR to equal the desired output bias value.

4/00

UDC 3300 Controller Product Manual

191

Page 203
Image 203