3.16Loop 2 Control Parameters Set Up Group

Introduction

Function prompts

The functions listed in this group define how Loop 2 of a Two Loop process controller will control the process.

Only available on Expanded Controller Model DC330E-XX-XXX.

Table 3-13 lists all the function prompts in the Control 2 Set Up group.

Table 3-13 Control 2 Group Function Prompts

Function Prompt

Lower Display

PV 2 SRC

FORCE MA

PID SETS

SW VALUE

LSP’S

RSP SRC

AUTOBIAS

SPTRACK

SP HiLIM

SP LoLIM

ACTION

Function

Name

Process Variable Source

Force Manual

Tuning Parameter Sets

Automatic Switchover Value

Local Setpoint Source

Remote Setpoint Source

Automatic Bias

Local Setpoint Tracking

Setpoint High Limit

Setpoint Low Limit

Control Output Direction

Selections or

Range of Setting

Upper Display

INP 1

INP 2

IN AL1

IN AL2

INP 3

DISABL

LINK12

1ONLY 2KEYBD 2PV SW 2SP SW

GAIN S (Gain scheduling automatically disables Accutune for this loop)

Value in engineering units within PV or SP range limits

1ONLY TWO

THREE (Selection automatically disables RSP SRC)

NONE

INP 2

IN AL1

IN AL2

INP 3

ENABLE

DISABL

NONE

PV

RSP

0 to 100 % of PV span input in engineering units

0 to 100 % of PV span input in engineering units

DIRECT

REVRSE

Factory

Refer

Setting

to

 

 

INP 2

Section

 

4.12

 

 

DISABL

1 ONLY

0.00

1ONLY

NONE

DISABL

NONE

1000

0

REVRSE

60

UDC 3300 Process Controller Product Manual

4/00

Page 72
Image 72
Honeywell UDC 3300 manual Loop 2 Control Parameters Set Up Group, Control 2 Group Function Prompts, Inp