Procedure

The procedure for calibrating the Position Proportional output and

 

 

3 Position Step control output is listed in Table 8-3. Make sure

 

LOCKOUT in Tuning Set Up group is set to NONE. See Section 3 –

 

Configuration.

 

For Three Position Step Control Output models without Motor Position

 

Indication, do steps 1 and 2 only.

 

For Position Proportional Output and Three Position Step Control Output

 

models with Motor Position Indication, follow the entire calibration

 

procedure.

 

 

 

 

 

 

ATTENTION

These prompts only appear when position OUT ALG is

 

 

 

 

selected. If motor position for 3PSTEP is desired, first configure unit for

 

“position.” After calibration the unit can be switched to 3PSTEP.

Table 8-3

Position Proportional and 3 Position Step Output Calibration Procedure

Step

1

Description

Enter Calibration Mode

Press

SET UP

Action

until you see

Upper Display

CALIB

Lower Display

POS PROP

2

3

Set Motor Traverse Time

NOTE: This is the time it takes the motor to travel from 0 % to 100 %.

Select Automatic or Manual Calibration

FUNCTION

LOOP 1/2

or

FUNCTION

LOOP 1/2

until you see:

Upper Display

a value

Lower Display

MTR TIME

until the proper motor stroke time is reached (see the motor specs or measure the time)

Range of setting = 5 to 1800 Seconds

until you see:

Upper Display

DISABLE

Lower Display

POS PROP

You can calibrate the controller output manually or let the controller calibrate the output automatically.

If the slidewire has never been calibrated, you must use DO AUTO first. In the “Automatic Calibration Mode” (DO AUTO), the controller relays automatically move the motor in the proper direction.

If desired, however, the motor may be manually positioned to 0 % and 100 % positions. Disconnect the relay wires. Use DO MAN. In the “Manual Calibration Mode” (DO MAN), the motor does not move. Instead, the existing 0 % and 100 % values may be changed with the or key.