Line voltage wiring

This equipment is suitable for connection to 90-264 Vac or 24 Vac/dc,

 

50/60 Hz, power supply mains. It is the user’s responsibility to provide a

 

switch and non-time delay (North America), quick-acting, high breaking

 

capacity, Type F, (Europe) 1/2 A, 250 V fuse(s) or circuit-breaker for 90-

 

264 V; or 1 A, 125 V fuse or circuit breaker for 24 Vac/dc operation, as

 

part of the installation. The switch or circuit-breaker should be located

 

close to the controller, within easy reach of the operator. The switch or

 

circuit-breaker should be marked as the disconnecting device for the

 

controller (4 mm2).

 

 

 

 

 

CAUTION

Applying 90-264 Vac to a controller rated for 24 Vac/dc

 

 

 

will severely damage the controller and is a fire and smoke hazard.

 

When applying power to multiple instruments, make sure that sufficient

 

current is supplied. Otherwise, the instruments may not start up normally

 

due to the voltage drop caused by the in-rush current.

 

Figure 2-5 shows the wiring connections for line voltage.

 

Figure 2-5

Line Voltage Wiring

 

 

 

 

1

Ground

2

Hot

AC/DC

 

Line

Neutral

Voltage

 

 

10

L1

11

L2/N

12

22

13

23

14

24 15

25

16

2617

27

1

2

3

4

5

6

7

8

9

22607

1PROTECTIVE BONDING (grounding) of this controller and the enclosure in which it is installed, shall be in accordance with National and local electrical codes. To minimize electrical noise and transients that

may adversly affect the system, supplementary bonding of the controller enclosure to a local ground, using a No. 12 (4 mm 2 ) copper conductor, is recommended.

2Provide a switch and non-time delay (North America), quick-acting, high breaking capacity, Type F, (Europe) 1/2 A, 250 V fuse(s) or circuit-breaker for 90-264 V; or 1 A, 125 V fuse or circuit breaker for 24 Vac/dc operation, as part of the installation.

4/00

UDC 3300 Controller Product Manual

19

Page 31
Image 31
Honeywell UDC 3300 manual Controller 4 mm2, Due to the voltage drop caused by the in-rush current, Line voltage wiring