Honeywell UDC 3300 manual Configure

Models: UDC 3300

1 294
Download 294 pages 16.21 Kb
Page 44
Image 44

Transmitter power for 4-20 mA 2-wire transmitter—open collector alarm 2 output

The wiring diagram example shown in Figure 2-19 (Model DC330X-XT-XXX) provides 30 Vdc at terminals 5 and 6 with the capability of driving up to 22 mA, as required by the transmitter which is wired in series.

If the transmitter terminal voltage must be limited to less than 30 volts, you can insert a zener diode between the positive transmitter terminal and terminal 5. For example, an IN4733A zener diode will limit the voltage at the transmitter to 25 Vdc.

Configure:

A2S1TYPE = NONE

A2S2TYPE = NONE

Figure 2-19 Transmitter Power for 4-20 mA 2-wire Transmitter Using Open Collector Alarm 2

Output—Model DC330X-XT-XXX

 

10

1

L1

11

2

L2/N

12

3

22

13

4

23

14

+ 5

24

15

6

25

16

7

26 +

17

8

27

 

9

250 ohm

 

 

resistor

 

 

If necessary, install zener diode here to reduce voltage at transmitter.

2-wire Transmitter

+

24171

32

UDC 3300 Controller Product Manual

4/00

Page 44
Image 44
Honeywell UDC 3300 manual Configure