Honeywell UDC 3300 manual Input 3 Parameters Set Up Group

Models: UDC 3300

1 294
Download 294 pages 16.21 Kb
Page 69
Image 69

3.14Input 3 Parameters Set Up Group

Introduction

Function prompts

This data deals with various parameters required to configure Input 3.

Table 3-11 lists all the function prompts in the Input 3 Set Up group.

Function Prompt

Lower Display

IN3 TYPE*

XMITTER3

Table 3-11

Function

Name

Input 3 Actuation Type

Transmitter Characterization

Input 3 Group Function

Selections or

Range of Setting

Upper Display

DISABL 0-20mA 4-20mA 0-5 V 1-5 V

B TC

S TC

E TC H

T TC H

E TC L

T TC L

J TC H

W TC H

J TC L

W TC L

K TC H

100 PT

K TC L

100 LO

NNM H

200 PT

NNM L

500 PT

NM90 H

RAD RH

NM90 L

RAD RI

NIC TC

LINEAR

R TC

SQROOT

Factory Setting

DISABL

LINEAR

Refer

to

Section

4.10

IN3 HI

Input 3 High Range Value

 

(Linear Inputs only)

IN3 LO

Input 3

Low Range Value

 

(Linear Inputs only)

RATIO 3

Input 3

Ratio

BIAS IN3

Input 3

Bias

 

 

 

FILTER 3

Input 3

Filter

*Not available on DC330B

–999. to 9999. floating (in engineering units)

–999. to 9999. floating (in engineering units)

–20.00 to 20.00

–999. to 9999.

(in engineering units)

0 to 120 seconds

1000

0

1.000

0

0

4/00

UDC 3300 Process Controller Product Manual

57

Page 69
Image 69
Honeywell UDC 3300 manual Input 3 Parameters Set Up Group, Input 3 Group Function Selections or Range of Setting