Set switchover value

If you select 2 PVSW or 2 SPSW, you must set a value at which the sets

 

will switch over. The procedure in Table 5-17 shows you how to set this

 

value. This procedure assumes that you are still in the Control Set Up

 

group from Table 5-16.

Step

1

Table 5-17 Procedure for Setting Switchover Values

Operation

 

Press

 

 

 

 

Action

Select

 

 

 

until you see:

 

FUNCTION

 

Switchover value

 

 

 

Upper Display

 

L1/L2

 

 

function

 

 

 

 

 

 

 

The switchover

 

 

 

 

 

 

 

 

 

 

 

assuming you

 

 

 

 

value

 

 

 

 

 

 

Lower Display

 

 

are still in

 

 

 

 

 

 

 

 

 

Control Set Up

 

SW VALUE

 

 

 

 

group

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or

to select the switch-over value in the upper

 

 

display.

 

 

 

 

 

 

 

 

 

 

 

 

 

Set tuning constant values for each set

There are specific tuning constants that must be set for each set. The procedure in Table 5-18 shows you how to access these constants and change their values.

Table 5-18 Procedure for Setting Tuning Constant Values

Step

1

2

Operation

Select Tuning Set Up Group

Select the tuning constants

Press

SET UP

FUNCTION

LOOP 1/2

or

Action

until you see:

Upper Display

SET UP

Lower Display

TUNING

to successively display the following constants:

Upper Display

The tuning constant value

Lower Display

PROP BD or GAIN*

RATE*

RSET*

CYC SEC or CYC SX3*

PROP BD2 or GAIN2**

RATE 2**

RSET2**

CYC2 SEC or CYC2 SX3**

To change the value of any of the above listed prompts in the lower display.

*PIDSET1 will be used when PV or SP, whichever is selected, is greater than the switch-over value.

**PIDSET2 will be used when PV or SP, whichever is selected, is less than the switch- over value.

4/00