Function Prompt

Lower Display

OUT RATE

ATTENTION

Does not apply to 3 Position Step Control algorithm.

Function

Name

Output Change Rate

Selections or

Range of Setting

Upper Display

ENABLE

DISABL

Factory Setting

DISABL

Refer

to

Section

4.11

PCT/M UP

PCT/M DN

OUTHiLIM

OUTLoLIM

I Hi LIM

I Lo LIM

DROPOFF

DEADBAND

OUT HYST

FAILMODE

FAILSAFE

SW_FAIL

Output Rate Up Value

Output Rate Down Value

High Output Limit

Low Output Limit

High Reset Limit

Low Reset Limit

Controller Dropoff Value

Output Relay Deadband

Output Relay Hysteresis

Failsafe Mode

Failsafe Output Value for all outputs except 3P Step

Failsafe Output Value for 3P Step

PDMR/Position Proportional motor position when slidewire fails

0 to 9999 % per minute

0 to 9999 % per minute

–5.0 to 105 % of output

–5.0 to 105 % of output

Within the range of the output limits

Within the range of the output limits

–5 to 105 % of output

Time Duplex: –5.0 to 25.0 %

On/Off Duplex: 0.0 to 25.0 %

Position Prop. and 3P Step:

0.5to 5.0 %

0.0to 100.0 % of PV Span for On/Off control.

NO LAT

LATCH

Set within the range of the output limits. 0 to 100 %

0 PCT (motor goes to closed position) 100PCT (motor goes to open position)

0 PCT (motor goes to closed position) 100PCT (motor goes to open position)

0

0

100

0.0

100.0

0.0

0

1.0

0.5

NO LAT

0.0

- -

MAN OUT

AUTO OUT

PBorGAIN

MINorRPM

Power-up Preset Output for Manual Output

Power-up Preset Output for Automatic Output

Proportional Band or Gain Units

Reset Units

Within the range of output limits

Within the range of output limits

PB PCT

GAIN

RPM

MIN

- -

- -

GAIN

MIN

4/00

UDC 3300 Process Controller Product Manual

59

Page 71
Image 71
Honeywell UDC 3300 manual OUT Rate, Pct/M Up Pct/M Dn, Dropoff Deadband OUT Hyst Failmode Failsafe Swfail, MAN OUT Auto OUT