Using TUNE at start-up for duplex (heat/cool)

After TUNE or TUN+PV has been enabled, use the procedure in Table 5-36 to use TUNE at start-up for duplex (heat/cool) control.

Table 5-36 Procedure for Using TUNE at Start-up for Duplex

Step

Action

 

 

1Heat Zone:

Adjust Local Setpoint 1 to a value within the Heat zone.

Put the controller in Automatic mode.

• Press the LOWER DISPLAY and keys simultaneously to initiate

Heat tuning.

The output will cycle between 50 % and 100 % (or high output limit). A large T appears in the upper display until tuning is completed and final Heat parameters are entered for PID set 1 in the Tuning group.

2Cool Zone:

Adjust Local Setpoint 2 to a value within the Cool zone.

Put the controller in Automatic mode.

• Press the LOWER DISPLAY and keys simultaneously to initiate

Cool tuning.

The output will cycle between 0 % and 50 % (or low output limit). A large T appears in the upper display until tuning is completed and final Cool parameters are entered for PID set 2 in the Tuning group.

How SP tuning works SP tuning will continually adjust the Gain or Proportional Band (P), Reset (I), and Rate (D) tuning constants in response to setpoint changes.

ATTENTION

SP tuning is not available on Basic Model DC330B.

SP tuning handles all Local and Computer setpoint changes. It uses time domain analysis, and the rule based expert system techniques to identify the two most dominant process lags plus any dead time. It then automatically readjusts the PID parameters as necessary. It does this while controlling to setpoint in automatic (closed loop) control mode.

These calculated PID values can be changed, if desired, whenever the tuning is not active. Tuning can be aborted by pushing the

Setpoint changes

MANUAL/AUTO key to return to the manual mode.

Two criteria are available—Normal and Fast—through configuration.

During start-up, or whenever the setpoint changes beyond the “SP Change” value, SP tuning employs time domain analysis to tune the process at any desired setpoint without any prior initialization or process knowledge.