Lower Display

Prompt

XMITTER

ANALYTIC*

* Expanded models only

IN1 HI

Upper Display

Range of Setting

or Selection

Select one from the columns below

B TC

S TC

E TC H

T TC H

E TC L

T TC L

J TC H

W TC H

J TC L

W TC L

K TC H

100 PT

K TC L

100 LO

NNM H

200 PT

NNM L

500 PT

NM90 H

RAD RH

NM90 L

RAD RI

NIC TC

LINEAR

R TC

SQROOT

 

ANALYTIC

 

 

NONE

PH

ORP mV

CONDmS

CONDuS

RSTVM^

TDS PPm

TDS PPb

CONCPt

DO PPm

DO PPb

–999. To 9999. Floating (in engineering units)

Parameter

Definition

TRANSMITTER CHARACTERIZATION— This selection lets you instruct the controller to characterize a linear input to represent a non-linear one.

ATTENTION Prompt only appears when a linear actuation is selected at prompt IN1 TYPE.

FOR EXAMPLE:

If input 1 is a 4 to 20 mA signal, but the signal represents a type K thermocouple, select K TC H and the controller will characterize the 4 to 20 mA signal so that it is treated as a type K thermocouple input (high range).

Parameter definitions are the same as in IN1 TYPE.

Analytic Input Selections and Ranges— This prompt appears only when XMITTER is set to ANALYTIC. Choosing an Analytic setting here will set the Input Range to appropriate Hi and Low values for that analytical application. You can adjust the Input Range if you want.

NONE

Input Hi

Input Low

as configured

as configured

pH

14.00

0.00

ORP

1600

–999

(millivolts)

 

 

CONDUCTIVITY

20.00

0.00

(milli Siemens)

 

 

CONDUCTIVITY

2000

0.00

(micro Siemens)

 

 

RESISTIVITY

2000

0.00

(Megaohms)

 

 

TOTALDISSOLVEDSOLIDS

9999

0.00

(parts per million)

 

 

TOTALDISSOLVEDSOLIDS

9999

0.00

(parts per billion)

 

 

CONCENTRATION

20.00

0.00

(parts per thousand)

 

 

DISSOLVED OXYGEN

20.00

0.00

(parts per million)

 

 

DISSOLVED OXYGEN

2000

0.00

(parts per billion)

 

 

 

 

 

INPUT 1 HIGH RANGE VALUE in engineering units is displayed for all inputs but can only be configured for linear or square root transmitter characterization.

Scale the #1 input signal to the display value you want for 100 %.

EXAMPLE:

Actuation (Input) = 4 to 20 mA

Process Variable = Flow

Range of Flow = 0 to 250 Gal/Min

High Range display value = 250

Then 20 mA = 250 Gal/Min

The control setpoint will be limited by the range of units selected here.

4/00

UDC 3300 Process Controller Product Manual

113