Honeywell UDC 3300 Output Algorithm Parameters Set Up Group, Out Alg, OUT2 ALG Rlystate, RLY Type

Models: UDC 3300

1 294
Download 294 pages 16.21 Kb
Page 65
Image 65

3.11Output Algorithm Parameters Set Up Group

Introduction

Function prompts

This data deals with various Output types that are available for use in the controller. It also lists the Digital Output Status, the Current Duplex functionality, and Relay Time Cycle increments.

Table 3-8 lists all the function prompts in the Output Algorithm Set Up group.

Table 3-8 Output Algorithm Group Function Prompts

Function Prompt

Lower Display

OUT ALG

Function

Name

Loop 1 Output Algorithm

Selections or

Range of Setting

Upper Display

TIME

Time Simplex

CURRNT

Current Simplex

POSITN

Position Proportional

TIME D

Time Duplex

CUR D

Current Duplex

CUR TI

Current/Time Duplex

TI CUR

Time/Current Duplex

 

 

Factory Setting

CURRNT

Refer

to

Section

4.7

4–20 RNG

OUT2 ALG*

RLYSTATE

Current Duplex Range

Loop 2 Output Algorithm

Digital Output State at 0 % Output

100PCT

 

100PCT

50 PCT

 

 

 

 

 

NONE

 

CURRNT

TIME

 

 

CURRNT

 

 

CUR D

 

 

CUR TI

 

 

TI CUR

 

 

 

 

 

1OF2OF

(Output relays 1 and 2 are

1OF2ON

 

both de-energized)

 

1ON2OF

(Output relay 1 is

 

 

energized, output relay 2

 

 

is de-energized)

 

1OF2ON

(Output relay 1 is de-

 

 

energized, output relay 2

 

 

is energized)

 

1ON2ON

(Output relays 1 and 2 are

 

 

both energized)

 

 

 

 

RLY TYPE

Relay Cycle Time Increments

MECHAN

(Cycle time in one second

MECHAN

 

 

 

 

increments)

 

 

 

 

SOL ST

(Cycle time in 1/3 second

 

 

 

 

 

increments: 1 = .33

 

 

 

 

 

seconds, 120 = 40

 

 

 

 

 

seconds)

 

 

 

 

 

 

 

 

*Not available on DC330B

 

 

 

 

 

 

 

 

 

4/00

UDC 3300 Process Controller Product Manual

53

Page 65
Image 65
Honeywell UDC 3300 Output Algorithm Parameters Set Up Group, Output Algorithm Group Function Prompts, Out Alg, RLY Type