Lower Display

Prompt

Upper Display

Range of Setting

or Selection

Parameter Definition

 

8SEG CH2

 

8 SEGMENT CHARACTERIZER #2— A second eight

 

 

 

 

segment characterizer can be applied to either

 

 

 

 

Input 1, Input 2, Output 1, or Output 2.

 

 

 

DISABL

DISABLE— Disables characterizer.

 

 

 

INPUT1

INPUT 1— Characterizer applied to Input 1.

 

 

 

INPUT2

INPUT 2— Characterizer applied to Input 2.

 

 

 

L1 OUT

LOOP 1 OUTPUT— Characterizer applied to Loop 1

 

 

 

 

Output. (NOTE 1)

 

 

 

L2 OUT

LOOP 2 OUTPUT— Characterizer applied to Loop 2

 

 

 

 

Output.

 

 

 

 

There are eight (Xn) Input values and eight (Yn) Output

 

 

 

 

values to be selected. The following rules apply:

 

 

 

 

• When Input 2 is used, Input 2 Ratio and Bias are

 

 

 

 

applied to the Xn Values.

 

 

 

 

• When one of the Loop outputs are selected, the Xn

 

 

 

 

Input values are the Output from the control algorithm,

 

 

 

 

and the Yn Output is the final control element action.

 

 

 

 

This application is useful for non-linear control elements

 

 

 

 

or Process Variable.

 

 

 

 

A simple example is shown in Figure 4-2.

 

 

 

 

 

 

 

 

 

 

ATTENTION The X values below should be entered as increasing values (from 0% to 100%) from N=0 to 8.

X0 VALU2

0.00 to 99.99 %

X0 INPUT VALUE (X AXIS)

X1 VALU2

0.00 to 99.99 %

X1 INPUT VALUE (X AXIS)

X2 VALU2

0.00 to 99.99 %

X2 INPUT VALUE (X AXIS)

X3 VALU2

0.00 to 99.99 %

X3 INPUT VALUE (X AXIS)

X4 VALU2

0.00 to 99.99 %

X4 INPUT VALUE (X AXIS)

X5 VALU2

0.00 to 99.99 %

X5 INPUT VALUE (X AXIS)

X6 VALU2

0.00 to 99.99 %

X6 INPUT VALUE (X AXIS)

X7 VALU2

0.00 to 99.99 %

X7 INPUT VALUE (X AXIS)

X8 VALU2

0.00 to 99.99 %

X8 INPUT VALUE (X AXIS)

Y0 VALU2

0.00 to 99.99 %

Y0 INPUT VALUE (Y AXIS)

Y1 VALU2

0.00 to 99.99 %

Y1 INPUT VALUE (Y AXIS)

Y2 VALU2

0.00 to 99.99 %

Y2 INPUT VALUE (Y AXIS)

Y3 VALU2

0.00 to 99.99 %

Y3 INPUT VALUE (Y AXIS)

Y4 VALU2

0.00 to 99.99 %

Y4 INPUT VALUE (Y AXIS)

Y5 VALU2

0.00 to 99.99 %

Y5 INPUT VALUE (Y AXIS)

Y6 VALU2

0.00 to 99.99 %

Y6 INPUT VALUE (Y AXIS)

Y7 VALU2

0.00 to 99.99 %

Y7 INPUT VALUE (Y AXIS)

Y8 VALU2

0.00 to 99.99 %

Y8 INPUT VALUE (Y AXIS)

4/00

UDC 3300 Process Controller Product Manual

105

Page 117
Image 117
Honeywell UDC 3300 manual Segment Characterizer #2- a second eight, X0 VALU2